EMCOR Facilities Services Joe Tate 4 Brocade PKWY Broomfield CO. 80021 303-884-1536
[email protected] 0480 BRM Brocade UPS Annual Testing UPS DC1 06/17/2015 Prepared for: Broomfield Brocade Communications Systems, Inc Ron Anthony Facilities Maintenance and Operations (303) 319 - 8353
[email protected] MDC: 6/17/2015 Voltage: Primary AIC as metered ZΩ UPS Model: E / A - BØ: 492.7 I / AØ: 118.2 AØ - ZΩ: 0.10 1 DC1 E / B - CØ: 492.7 I / BØ: 117.7 BØ - ZΩ: 0.11 0 DC2 E / C - AØ: 490.6 I / CØ: 118.2 CØ - ZΩ: 0.10 0 OEM E / AØ: 284.5 kVA / AØ: 33.6 AMPS: 0 SQA E / BØ: 284.5 kVA / BØ: 33.5 3Ø ASYM: 8263.3 E / CØ: 283.3 kVA / CØ: 33.5 kVA 3Ø: 100.6 UPS Unit: 6/16/2015 Panel : IP: 78.8% WO# Voltage: Power Used: AØ - ZΩ: 0.33 A-Bø: 479.2 BØ - ZΩ: 0.24 B-Cø: 480.3 kVA / AØ: 26.5 CØ - ZΩ: 0.33 A-Cø: 479.0 kVA / BØ: 24.9 AMPS: Aø: 276.7 kVA / CØ: 27.9 3Ø ASYM: 2831.9 Bø: 277.3 KVA 3ø: 79.3 Cø: 276.6 Power Available: Rated KVA: 500.0 0.8 Current: Rated KW: 400.0 Aø: 95.7 Actual PF%: 0.96 Bø: 89.8 KW: 76.1 DC1: 16 800 Cø: 100.9 KVA %: 15.9 DC2: 12 500 Nuet Amps: 9.6 KW%: 19.0 OEM: 12 550 N Inbal: 10.1% SQA: 12 550 DC1: 4/1/2013 Datasafe 16HX800F Months in Service: 27 KWh: # of Strings: 2 E: 16.0 DC2: 1/1/2013 sprinter S12V500F DC String E: 521.5 768 # Batteries: 30 I: 800.0 OEM: 3/1/2014 Sprinter S12V550F AC Ripple I: 3.2 Avg Float VDC: 17.38 kW: 12.8 SQA: 5/1/2015 Sprinter S12V550F DC1 Sinewaves Line Side Voltage Sinewave Line Side Current Sinewave Load Side Voltage Sinewave Load Side Current Sinewave Page 2 EMCOR Facilites Services 554.2 1 16 1.338 0.1 800 1 DC VOLTS AC MV DC VOLTS AC MV 1 17.745 3111 21 17.710 3286 2 17.714 3115 22 17.669 3637 Average dcV: 17.687 3 17.692 3115 23 17.605 3650 High dcV: 17.745 4 17.718 3630 24 17.652 3641 low dcV: 17.563 5 17.706 3284 25 17.655 3296 6 17.714 3113 26 17.653 3643 Average Ω: 3434.133 7 17.675 3463 27 17.605 3476 High Ω: 3652 8 17.719 3630 28 17.632 3650 Low Ω: 3111 9 17.718 3630 29 17.621 3652 17.745 17.71 10 17.725 3282 30 17.563 3485 17.675 17.563 11 17.729 3627 31 17.745 3652 12 17.718 3457 32 3111 3286 13 17.729 3282 33 14 17.706 3113 34 15 17.716 3457 35 16 17.729 3282 36 17 17.695 3634 37 18 17.677 3638 38 19 17.721 3457 39 20 17.695 3288 40 NOTES: CELL AH: UPS Name: STRING VOLTAGE AC: BATTERY STRING: DC1 DC CURRENT: STRING VOLTAGE DC: AC RIPPLE CURRENT: CELL VDC: Datasafe 16HX800F BATTERY MAKE: Battery cab #: 17.25 17.50 17.75 18.00 18.25 2000 3000 4000 5000 CAB_1 V ol ta ge (V ) In t. R es . ( u- O hm s) Cell Number 3 6 9 12 15 18 21 24 27Cell Number Voltage 17.692 17.714 17.718 17.718 17.716 17.677 17.710 17.652 17.605 Internal Res 3115.000 3113.000 3630.000 3457.000 3457.000 3638.000 3286.000 3641.000 3476.000 17.25 17.50 17.75 18.00 18.25 2000 3000 4000 Apr 2015 May Jun CAB_1 V ol ta ge (V ) In t. R es . ( u- O hm s) Read Date 554.3 1 16 1.327 0.1 800 2 DC VOLTS AC MV DC VOLTS AC MV 1 18.366 3280 21 18.089 3630 2 18.399 3450 22 18.011 3290 Average dcV: 18.125 3 18.246 3459 23 18.06 3632 High dcV: 18.473 4 18.473 3623 24 18.062 3453 Low dcV: 17.773 5 18.359 3627 25 18.05 3634 6 18.299 3630 26 18.105 3810 Average Ω: 3449.233 7 18.164 3096 27 17.992 3288 High Ω: 3810 8 18.115 3270 28 17.962 3465 Low Ω: 3096 9 18.183 3096 29 17.912 3641 18.473 18.105 10 18.169 3268 30 17.923 3638 17.773 17.912 11 18.135 3098 31 3632 3810 12 18.091 3272 32 3096 3288 13 17.961 3286 33 14 17.773 3282 34 15 18.223 3450 35 16 18.131 3459 36 17 18.265 3632 37 18 18.125 3630 38 19 18.013 3461 39 20 18.095 3627 40 NOTES: DC1 UPS Name: STRING VOLTAGE DC: STRING VOLTAGE AC: DC CURRENT: BATTERY MAKE:Batter cab #: BATTERY STRING: AC RIPPLE CURRENT: Datasafe 16HX800F CELL VDC: CELL AH: 17.5 18.0 18.5 19.0 2000 3000 4000 5000 CAB_2 V ol ta ge (V ) In t. R es . ( u- O hm s) Cell Number 3 6 9 12 15 18 21 24 27Cell Number Voltage 18.246 18.299 18.183 18.091 18.223 18.125 18.089 18.062 17.992 Internal Res 3459.000 3630.000 3096.000 3272.000 3450.000 3630.000 3630.000 3453.000 3288.000 17.75 18.00 18.25 18.50 18.75 2000 3000 4000 5000 Apr 2015 May Jun CAB_2 V ol ta ge (V ) In t. R es . ( u- O hm s) Read Date EMCOR Facilities Services Summery page 06/12/2014 Cabinet 1: All batteries are showing good Cabinet 2: All batteries are showing good Cabinet 3: N/A Summery: UPS appears to be in very good working condition. No problems found. If There are any questions please feel free to contact me Joe Tate EMCOR Facilities Broomfield Brocade 303-884-1536 Replaced Filter Media. UPS Name Installation Date: Age in months: Battery Date Code Battery Age in months DC Oil filled Capss: DC_O age in months AC Oil filled Caps: AC_O age in months Filters: Filters Age in months: Firmware: Firmware age in months* DC Electrolitic Caps DC_E age in months 06/17/15 UPS DC1 3/1/2013 28 3/1/2013 28 3/1/2013 28 3/1/2013 28 6/18/2015 0 3/1/2013 28 3/1/2013 28 UPS DC2 6/10/2009 73 1/1/2013 30 6/10/2009 73 6/10/2009 73 6/17/2015 0 1/1/2013 30 6/10/2009 73 UPS OEM 8/22/2003 144 3/1/2014 16 5/24/2010 62 5/24/2010 62 6/16/2015 0 5/24/2010 62 8/22/2003 144 UPS SQA 8/22/2003 144 5/15/2015 1 5/24/2010 62 5/24/2010 62 6/16/2015 0 5/24/2010 62 8/22/2003 144 Watch closely at: 200 48 72 72 9 60 200 Recommend replace: 224 60 84 84 12 80 224 Needs Replacing!!! 248 72 96 96 15 100 248 * Firmware may not be available for older models. Contact OEM for details. SqD HA351000 1000A Panel H2D1 MLO SqD MJ800 AC Input SqD MJ800 Maint. Bypass Input Breaker CB1 Maintenance Bypass Breaker Static Switch Input Contactor (K1) UPM1 Input Contactor (K1) UPM2 Backfeed Contactor (K5) Rectifier UPM1 Rectifier UPM2 Inverter UPM1 Inverter UPM2 Output Contactor (K3) UPM1 Output Contactor (K3) UPM2 Battery Converter UPM1 Battery Converter UPM2 Battery Contactor (K2) UPM1 Battery Contactor (K2) UPM2 Battery Cabinet 1 Battery Cabinet 2 Maintenace Isolation Breaker MDC2 2500A Bus 1000A Bus Single Feed Kit EATON 9395 UPS DC1 "A Bus" 500kVA / 400kW 480V 3Ø - 480V 3Ø Joe Tate EMCOR Facilities Services Broomfield Brocade
[email protected] 303-884-1536 EATON 9395 Maintenance Bypass Module AC 3Ø Critical Load 0480 BRM Brocade UPS Testing Joe Tate | (303) 884-1536 |
[email protected] Inspection Summary File name UPS DC1 (1).is2 Inspection Date and Time 1/1/2000 3:45:56 PM Severity File name UPS DC1 (2).is2 Inspection Date and Time 1/1/2000 3:46:29 PM Severity File name UPS DC1 (3).is2 Inspection Date and Time 1/1/2000 3:46:47 PM Severity File name UPS DC1 (4).is2 Inspection Date and Time 1/1/2000 3:47:17 PM Severity File name UPS DC1 (5).is2 Inspection Date and Time 1/1/2000 3:47:38 PM Severity File name UPS DC1 (6).is2 Inspection Date and Time 1/1/2000 3:47:57 PM Severity 0480 BRM Brocade UPS Testing Joe Tate | (303) 884-1536 |
[email protected] UPS DC1 (1).is2 1/1/2000 3:45:56 PM Visible Light Image Graph Image Info IR Sensor Size 160 x 120 0480 BRM Brocade UPS Testing Joe Tate | (303) 884-1536 |
[email protected] UPS DC1 (2).is2 1/1/2000 3:46:29 PM Visible Light Image Graph Image Info IR Sensor Size 160 x 120 0480 BRM Brocade UPS Testing Joe Tate | (303) 884-1536 |
[email protected] UPS DC1 (3).is2 1/1/2000 3:46:47 PM Visible Light Image Graph Image Info IR Sensor Size 160 x 120 0480 BRM Brocade UPS Testing Joe Tate | (303) 884-1536 |
[email protected] UPS DC1 (4).is2 1/1/2000 3:47:17 PM Visible Light Image Graph Image Info IR Sensor Size 160 x 120 0480 BRM Brocade UPS Testing Joe Tate | (303) 884-1536 |
[email protected] UPS DC1 (5).is2 1/1/2000 3:47:38 PM Visible Light Image Graph Image Info IR Sensor Size 160 x 120 0480 BRM Brocade UPS Testing Joe Tate | (303) 884-1536 |
[email protected] UPS DC1 (6).is2 1/1/2000 3:47:57 PM Visible Light Image Graph Image Info IR Sensor Size 160 x 120 0480 BRM Brocade UPS Testing Joe Tate | (303) 884-1536 |
[email protected] Summary ref#0480 BRM Broomfield UPS Testing All Batteriy Temps and associated DC Breakers are within range for the low current that is passing through them. Thanks Joe Tate EET / Master Electrician